DI-M9204 Digital Manual Call Point
 
 
Feature
  • • Electronically addressed. The address can be modified in field.
  • • Alarming by pressing, reset by a special key.
  • • Plug-in structure.
  • • Complies with UL38.

Specifications
  • Operating Voltage Loop 24V(16V~28V)
    Standby Current <=0.6mA
    Alarm Current <=1.8mA
    Indicator Red. Flashes every 3s normally. Steadily Illuminates after alarm.
    Type of Initiating Part Reusable
    Initiating Mode Pressing the glass manually
    Resuming Mode Manually resumed by a special key
    Programming Mode Electronically addressed
    Address Range Occupying one address, selectable within 1~242.
    Wiring Polarity-insensitive two-wire
    Ingress Protection Rating IP43
    Environmental Temperature -10°C~+50°C
    Relative Humidity <=95%, non condensing
    Material of Enclosure ABS
    Dimension (L×W×H) 87.1mm×87.1mm×58mm (with back box)
    Mounting Hole Distance 60mm
    Weight About 160g (with back box)
 
 
 