Home
>
Products
>
Fire Alarm System
>
Intelligent Modules
I-9319 Addressable Zone Monitor Unit
Download>>
Quotation>>
Feature
Interfaces with conventional fire detection equipment/panels etc
Can connect up to 15 detectors with Active EOL or up to 25 detectors with Resistor EOL
Ideal for integrating Sprinkler Zone Valve and Flow SwitchesElectronically addressed
Technical Specifications
Operating Voltage: 24VDC Loop, 24VDC Power Supply
Operating Current (loop):
Monitoring Current 1.5mA
Action Current 5mA
Capability: 15 conventional detectors
End of line: 4.7kΩ¸ resistor or AEOL
Action Resistance: 470~680¦¸
Operating Environment:
Temperature -10 ~ +50°C
Relative Humidity 95%
Dimension: 120mm x 80mm x 40mm