I-9401 Addressable Souder Beacon
 
 
Feature
  • Addressable combined flashing high intensity LED beacon and sounder
  • Two part plug-in construction with base mounted termination allowing easy installation and connection
  • Electronically addressed

Technical Specifications
  • Operating Voltage: 24VDC Loop, 24VDC Power Supply
  • Operating Current:
    Loop: Standby Current 0.8mA; Alarm Current 6.0mA
    Power Supply: Standby Current 10mA, Alarm Current 160mA
  • Alarm volume (SPL): 95dB @1 Metre
  • Wiring:

    Non-polarized 2-core for loop
    Non-polarized 2-core for power supply

  • Operating Environment:

    Temperature -10 ~ +50°C
    Relative Humidity 95%

  • Dimension: 144mm x 90mm x 57mm
 
 
 