I-9402 Addressable Sounder Base
 
 
Feature
  • Loop Powered Sounder
  • Can be used as a common base of detector or stand alone with a cover
  • Two addresses (one for Alert and one for Evacuate tones)
  • Compatible sound with I-9403 / C-9403 Sounder Flasher and I-9404 / C-9404 Sounder

Technical Specifications
  • Operating Voltage: 24VDC Loop
  • Operating Current:

    Standby Current 1mA
    Action Current 7mA

  • Loop capacity: 30 pieces per loop
  • Sound Output (SPL): 86dB @1 Metre
  • Operating Environment:

    Temperature -10 ~ +50°C
    Relative Humidity 95%

  • Dimension: Diameter 10cm, Height 3.5cm (without cover), 4.5cm (with cover)
 
 
 