| Feature 
								   ☆Loop powered.☆Electronically addressed by programmer.☆Optical Pathway 5 -100 Meters.
 ☆Maximum monitoring area: 14 x100=1400m2
 Maximum width: 14m
 ☆Combination of the emitting and receiving part makes mounting easy and optical pathway accurate.
 ☆Built-in microprocessor enables intelligent judgment about fire alarm and fault.
 ☆Easy alignment and commissioning via supporting of onboard laser pointer and digital signal intensity indication.
 ☆Self-diagnostic function can monitor the internal fault.
 ☆Drift compensation for factors changing, such as a certain of dust accumulation, positional excursion, and ageing transmitter.
 ☆Four sensitivity levels can be set in field.
 ☆LPCB Approved
 Technical Specifications
 
								   ☆Operating Voltage: 24VDC (16V~28V)Commissioning current: ≤ 20mA
 Standby current: ≤ 2mA
 Alarm current: ≤ 5mA
 ☆Angle of Adjusting -6°to +6°
 Maximum angular misalignment ±0.5°
 ☆Sensitivity Level:
 Level 1: 1.3dB
 Level 2: 1.8dB (factory default)
 Level 3: 2.3dB
 Level 4: 2.8dB
 ☆Operating Environment:
 Temperature: -10°C - +50°C
 Relative Humidity≤ 95%, non -condensing
 ☆Ingress Protection Rating:
 IP20 without glue-seal
 IP66 through glue-seal treatment
 ☆Material and Color of Enclosure: ABS, gray
 ☆Dimensions: 206mm X 95mm X 95mm
 ☆Weight: 450g
 
 |