								Feature 
							 
							    ☆Input port monitored with 4.7KΩ EOLR☆Normally open or normally closed contact input signal
 acceptable
 ☆Input port co-operates with output or works individually
 ☆Electronically addressed.Addresses can be modified in field
 ☆Built-in microprocessor and AD sampling technology
 ☆Rail mount or surface mount
 Technical Specifications
 
							    ☆Operating Voltage: Loop 24VDC (16VDC - 28VDC) Power Limited
 ☆Standby Current: ≤0.26mA
 ☆Action Current: Loop ≤0.7mA
 ☆Output Capacity: 2A@30 VDC,Normally-open/Closed
 ☆Programming: Electronically addressing
 ☆ Address Range:
 1 address, from 1 to 242
 2 addresses, from 1 to 241
 ☆ Indicator:
 Input LED: Red. lt lights in receiving feedbacks, lights 0.5s on,
 0.5s off in input faults, and flashes in other states
 Output LED: Red. lt lights in relay action.0.5s on and 0.5s off
 as there is output fault It turns off in other states
 ☆ Ingress Protection Rating: lP30
 ☆ Operating Temperature: -10°C~+55°C
 ☆ Relative Humidity: ≤95%,Non Condensing
 ☆ Material and Color of Enclosure: ABS, white(RAL9016)
 ☆ Dimension (LxWxH): 85.3mmx78mmx33mm
 ☆ Weight: About 66.5g
 |