Feature
☆Input port monitored with 4.7KΩ EOLR
☆Normally open or normally closed contact input signal
acceptable
☆Input port co-operates with output or works individually
☆Electronically addressed.Addresses can be modified in field
☆Built-in microprocessor and AD sampling technology
☆Rail mount or surface mount
Technical Specifications
☆Operating Voltage: Loop 24VDC (16VDC - 28VDC) Power
Limited
☆Standby Current: ≤0.26mA
☆Action Current: Loop ≤0.7mA
☆Output Capacity: 2A@30 VDC,Normally-open/Closed
☆Programming: Electronically addressing
☆ Address Range:
1 address, from 1 to 242
2 addresses, from 1 to 241
☆ Indicator:
Input LED: Red. lt lights in receiving feedbacks, lights 0.5s on,
0.5s off in input faults, and flashes in other states
Output LED: Red. lt lights in relay action.0.5s on and 0.5s off
as there is output fault It turns off in other states
☆ Ingress Protection Rating: lP30
☆ Operating Temperature: -10°C~+55°C
☆ Relative Humidity: ≤95%,Non Condensing
☆ Material and Color of Enclosure: ABS, white(RAL9016)
☆ Dimension (LxWxH): 85.3mmx78mmx33mm
☆ Weight: About 66.5g
|