								Feature 
							 
							    ☆Input port cable monitoring with 4.7KQ EOLR☆Monitoring power supply
 ☆Two indicators for fire and fault
 ☆Normally-open or Normally-close output automatically follows
 input port to change state
 ☆Electronically addressed.Addresses can be modified in field
 ☆Din-Rail mount or surface mount
 Technical Specifications
 
							    ☆Operating Voltage(Loop): Loop: 24VDC(16VDC-28VDC)☆Power Voltage: Loop:Power: 24VDC(20VDC-28VDC)
 ☆ Standby Current:
 ≤0.38mA(Loop)
 ≤10mA(Power)
 ☆ Action Current:
 ≤0.39mA(Loop)
 ≤60mA(Power)
 ☆Output Capacity: 2A@30VDC
 ☆Relay Output: NO or NC
 ☆Voltage of input Port: 16.8VDC-27.6VDC
 ☆Input Capacity: Up to 30 conventional detectors
 ☆Programming: Electronically addressed
 ☆Address Range: 1 address, from 1 to 242
 ☆ Indicator:
 Alarm LED: Red, illuminates in fire condition, quiet when 24V
 power is off and flashes in other states
 Fault LED: Yellow, it turns 0.5s on, 0.5s off when input fault
 occur, 0.2s on and 0.2s off when output faults occur,0.1s on
 and 0.9s off when ground faul occurs. lt lights steadily when
 loop faults occur and it turns off in other states
 ☆ Ingress Protection Rating: IP30
 ☆ Operating Temperature: -10°C-+55°C
 ☆ Relative Humidity: ≤95%,non-condensing
 ☆ Material and Color of Enclosure: ABS,white(RAL9016)
 ☆ Dimension(LxWxH): 85.3mmx78mmx33mm
 ☆ Weight: About 74.1g
 |