☆ 7-inch Touch Screen, 800 x480 resolution
☆ Support 1-6 loops in Class A style (additional battery box is
required if 6 loops fully loaded)
☆ 242 addressable devices per loop mixing various types of
devices, Max. 1452 addresses
☆ Max 8 ZCP panels ,each panel with individual programmable
buttons & LED indicators
☆ Multi-language support
☆ Graphic Cause and Effect programing AND,OR, NAND,NOR
logic, support virtual variable
☆ Auto learn panel hardware configuration and loop devices,
device type mismatch notice
☆ Detector chamber dirty level reporting, adjustdirty level
threshold
☆ History records of 100,000 events
☆ “Walk test", silent or audible
☆ Type A Type B Positive Alarm Sequence
☆ E-mail notification
☆ USB port for loading project database and firmware update
☆ Programing via PC or panel keypad and touch screen
☆ Support uSB dongle for securing project database
Technical Specifications
☆ Primary Supply:
110VAC~230VAC.
50/60Hz.3.0A~1.4A(Maximum Alarm)
☆ Battery: Two 12V/38Ah sealed lead-acid batteries,Max. Two
12V/65Ah (additional battery box required)
☆ Loop Capacity: 1~6 loops
☆ Device Capacity: 242 addresses per loop
☆ Loop Parameter:
Voltage: Nominal 24VDC
Average current: 130mA
Maximum alarm current: 300mA
Maximum wiring resistance: 18ohms(each line)
☆ Fire alarm and AUX outputs:
Fire alarm and AUX outputs
Class B.Power-limited
Output Voltage: Nominal 24DC
Max. Current: Totally 2.5A
☆ Input Rating: Maximum current: 1.7mA (short circuit)
☆ Printer: Thermal, ASCll code printer
☆ LCD Display: 7" TFT touch screen,800x480
☆ Network Nodes: Max. 250 panels
☆ PC Port: LAN/USB interface
☆ Protection: IP30
☆ Operating Environment: -5~50°C, ≤93% RH, non-condensing
☆ Dimensions: 516mm(W)x 840mm(H)x180mm(D)
|